Dynasty UPS Sealed Lead Acid Batteries

 

Electrical Specifications

  • Operating Temperature Range:
    • Discharge: -40ºC to +60ºC
    • Charge: -20ºC to +50ºC
  • Nominal Operating Temp. Range: 23ºC to 27ºC
  • Float Charging Voltage:
    • 12 volt units: 13.5V to 13.8 VDC
    • 6 volt units: 7.2 to 7.4 VDC
  • Maximum Charging Current Limit: C/5 amperes
  • AC Ripple from charger: 0.5% RMS or 1.5% of float charge voltage recommended for best results.
  • Self Discharge: Dynasty UPS batteries may be stored for up to 6 months at 25ºC and then a freshening charge is required. For higher temperatures the time interval will be shorter

Ancillary items

A full range of interconnect cables, terminal covers, open and cladded racks are available and can be tailored to fit in the space you have available. These products are supplied disassembled so that they can easily be transported and assembled on site.

Carrying harness with handles to ease the movement of batteries can be provided - please see batteries with carrying harness section for picture.

Standards & Compliances

The UK C&D Technology warehouse is approved to:
BS EN ISO 9002:1994.

The C&D Technologies inc. Dynasty Division operation is approved to:
ISO 9001:1994 for design and manufacture of lead-acid batteries.

Certain products are certified by Underwriters Laboratory:
UL924 MH11577N and certificates of conformance for specific products will be issued on request.

Back to Previous Section
All material on this site is © 2005 Pulsar Developments Ltd